November 26, 2026
CVE-2026-129713 Danfoss AK-SM 8xxA refrigeration system manager stack-based buffer overflow

CVE-2026-129713 is a stack-based buffer overflow in an unauthenticated CGI handler of Danfoss AK-SM 8xxA Series refrigeration controllers, rated 9.8 under CVSS v3.1 by CISA and 9.3 under CVSS v4.0 by Danfoss. No exploitation has been confirmed. Versions 5.4.0 and earlier are affected, and no fix exists yet: Danfoss plans one for software 5.5.x, so operators must keep these controllers off the internet for now.

CVE ID CVE-2026-129713
Product Danfoss AK-SM 8xxA Series (AK-SM 800A)
Flaw type Stack-based buffer overflow (CWE-121)
CVSS 9.8 (CVSS v3.1, CISA) / 9.3 (CVSS v4.0, Danfoss and CISA)
Exploitation / KEV No confirmed exploitation
Fixed version Not yet released (planned for 5.5.x)

What is CVE-2026-129713?

The flaw sits in a CGI handler of the controller’s web server that requires no login. According to the CVE record published by Danfoss, a remote attacker can send crafted HTTP or HTTPS POST requests to it. That corrupts memory and restarts the web server.

Danfoss describes code execution as possible but unproven. The record calls it “hypothetically potential arbitrary code execution with webserver privileges.” The attacker needs network access to the web interface. No authentication and no user interaction are required.

The AK-SM 800A manages refrigeration in supermarkets and cold storage sites, according to Claroty Team82. CISA’s advisory ICSA-26-328-03 lists Commercial Facilities as the affected critical infrastructure sector. It says the product is deployed worldwide. Danfoss has its headquarters in Denmark.

CISA scores the flaw 9.8 under CVSS v3.1 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). Danfoss, the CNA, rates it 9.3 under CVSS v4.0 (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H), and CISA repeats that score. The weakness is CWE-121.

Is CVE-2026-129713 being exploited?

No. CISA says no known public exploitation targeting this vulnerability has been reported to it. The CVE does not appear in the CISA Known Exploited Vulnerabilities catalog. No public proof-of-concept for this specific CVE has been confirmed.

On November 5, CISA, the FBI, HHS, USDA and the Department of Transportation published a joint fact sheet on industrial refrigeration and cold chain systems. It warns of global malicious activity against refrigeration controllers. It names no vendor and no CVE. Ireland’s NCSC advisory of November 13 says attacks since October 11 hit internet-exposed Danfoss, Dixell XWEB and Copeland XWEB interfaces. Nothing links those attacks to CVE-2026-129713.

Affected and fixed versions

Product Branch Affected versions Fixed version
Danfoss AK-SM 8xxA Series All 5.4.0 and earlier None yet – fix planned for upcoming 5.5.x

The range comes from Danfoss advisory DSA-2026-12-01, the CVE record and the CISA advisory. All three agree on 5.4.0 as the last affected release.

How to fix CVE-2026-129713

There is no patch to install today. Danfoss says the fix will ship in an upcoming AK-SM 800A Series release, version 5.5.x. It will also remove the option to disable Strict Mode in future releases. Plan the 5.5.x upgrade as soon as Danfoss publishes it.

If you cannot patch yet

Every site is in this position until 5.5.x arrives. Danfoss and CISA list these mitigations:

  • Do not expose the controllers directly to the internet, and do not assign them public IP addresses.
  • Restrict remote access through a secure VPN or another protected network architecture.
  • Run all affected devices in Strict Mode.
  • Use strong, unique passwords for all user and administrative accounts.
  • Follow the Danfoss AK-SM 800A security guidance page.

Network segmentation carries most of the load until then. CISA advises placing control networks behind firewalls and isolating them from business networks. The joint fact sheet adds a dedicated VLAN for OT devices, device and IP allowlisting, and logging. It also suggests setpoint limits with alerts on deviations.

Do not treat Strict Mode as a cure. Midnight Blue reports that one of its six unauthenticated bugs sits in the gateway that enforces Strict Mode. NCSC Ireland warns that updates, password changes and Strict Mode are not enough on their own for internet-exposed controllers.

How to check if you are affected

Any AK-SM 8xxA controller on software 5.4.0 or earlier is vulnerable. Next, confirm whether its web interface is reachable from the internet. Midnight Blue advises checking integrator-installed 4G modems as well as your own IP ranges. Also check the session control level. The options are backward compatible, permissive and strict. Midnight Blue says Strict has been the default since firmware 4.0.

Why it matters

Researcher Carlo Meijer of Midnight Blue reported six pre-authentication stack overflows in firmware up to 5.3.2. Most sit in unauthenticated CGI handlers, and one sits in the Strict Mode gateway. The write-up listed CVE IDs as pending, and that gap has now started to close. CISA credits Meijer with CVE-2026-129713. However, neither Danfoss nor CISA says which of the six bugs it covers.

The version range also grew. Midnight Blue tested 5.3.2, while Danfoss now confirms 5.4.0 is affected too.

The privilege level is an open question. Danfoss says code would run with web server privileges. Midnight Blue reports that the application it exploited on firmware 3.3.0 runs as root. It also found no stack canaries and no PIE in the binaries it checked.

The product has a long record of web interface flaws. Danfoss fixed CVE-2025-41450, an authentication bypass, in 4.2. CVE-2025-41451 and CVE-2025-41452 followed in 4.3.1. Midnight Blue notes that public exploits for older Danfoss flaws appeared within 48 hours of the attacks in France.

Timeline

Date Event
October 11, 2026 Attacks on internet-exposed refrigeration controllers begin in France (NCSC Ireland)
November 2, 2026 Second wave of attacks (NCSC Ireland)
November 5, 2026 CISA, FBI, HHS, USDA and DOT publish joint fact sheet
November 13, 2026 NCSC Ireland advisory on six unpatched AK-SM800A flaws
November 16, 2026 CVE-2026-129713 reserved
November 20, 2026 CVE-2026-129713 published by Danfoss
November 24, 2026 CISA releases ICSA-26-328-03